ÜRÜNLER

easyPower, ELC-PS ve PSG Power Supplies Series

Features

Power supplies easyPower, ELC-PS and PSG

Whether at the machine or on the plant, in the control panel or the service distribution – the easyPower, ELC-PS and PSG 24 V DC power supply units provide the right solution and design for any requirement.

  • These rail-mounted power supply units provide a reliable 1 phase and 3 phase supply for efficient operation
  • In addition to the wide range inputs and approval for worldwide use, these devices stand out on account of their optimum efficiency and large temperature range.
  • The short-circuit proof design and overload withstand capability ensure a safe power supply
  • The compact housing saves space and costs. The adjustable output voltage range of the PSG power supply ensures optimum adaptability.

Application:

With an output current of 1 A to 40 A, the power supply units are designed to supply machines and plants with low power requirements as well as large current loads.

PSG Power Supply Units

1-phase: 85 – 264 V AC (120 - 375 V DC) / 22 – 28 V DC, CE, UL, CSA, NEC Class II
2.5 A - PSG60N24RP

1-phase: 85 – 264 V AC (120 - 375 V DC) / 24 – 28 V DC, CE, UL, CSA
2.5 A - PSG60E24RM
5 A - PSG120E24RM
10 A - PSG240E24RM
20 A - PSG480E24RM

3-phase: 3 x 320 – 600 V AC, 2 x 360 – 600 V AC (450 – 800 V DC) / 24 – 28 V DC, CE, UL, CSA
2.5 A - PSG60F24RM
5 A - PSG120F24RM
10 A - PSG240F24RM
20 A - PSG480F24RM
40 A - PSG960F24RM

Redundancy modules: CE, UL , CSA
20 A - PSG480R24RM
40 A - PSG960R24RM
integrated O-Ring diode for parallel connection of N+1 power supplies

Buffe rmodule: CE, UL, CSA 20 A - PSG480B24RM
has the stored power needed to keep loads running through a short duration power failure:
250 ms @ 24 V DC / 20 A load
5 sec @ 24 V DC / 1 A load
parallel connection possible to increase buffering time
flexible Buffer mode (switchable):
Fixed mode: Buffering starts, when output voltage falls below 22 V DC
Dynamic mode: Buffering starts, when output voltage is decreased by > 1 V.

Other Pictures

Article No

Product Code

Product Description

172891

PSG60E24RM

Power Supplies - Mono Phase (100-240VAC / 24VDC ±2%) 2,5A

172892

PSG120E24RM

Power Supplies - Mono Phase (100-240VAC / 24VDC ±2%) 5A

172893

PSG240E24RM

Power Supplies - Mono Phase (100-240VAC / 24VDC ±2%) 10A

172894

PSG480E24RM

Power Supplies - Mono Phase (100-240VAC / 24VDC ±2%) 20A

172882

PSG60F24RM

Power Supplies - Three Phase (400-500VAC / 24VDC ±2%) 2,5A

172883

PSG120F24RM

Power Supplies - Three Phase (400-500VAC / 24VDC ±2%) 5A

172884

PSG240F24RM

Power Supplies - Three Phase (400-500VAC / 24VDC ±2%) 10A

172885

PSG480F24RM

Power Supplies - Three Phase (400-500VAC / 24VDC ±2%) 20A

 

PSG Power Supplies Unit

1-phase:
85 – 264 V AC (120 - 375 V DC) / 22 – 28 V DC, CE, UL, CSA, NEC Class II 2.5 A - PSG60N24RP

1-phase:
85 – 264 V AC (120 - 375 V DC) / 24 – 28 V DC, CE, UL, CSA
2.5 A - PSG60E24RM
5 A - PSG120E24RM
10 A - PSG240E24RM
20 A - PSG480E24RM

3-phase:
3 x 320 – 600 V AC, 2 x 360 – 600 V AC (450 – 800 V DC) / 24 – 28 V DC, CE, UL, CSA 2.5 A - PSG60F24RM
5 A - PSG120F24RM
10 A - PSG240F24RM
20 A - PSG480F24RM
40 A - PSG960F24RM

Redundancy modules:
CE, UL , CSA
20 A - PSG480R24RM
40 A - PSG960R24RM

 

integrated O-Ring diode for parallel connection of N+1 power supplies

Buffer module: CE, UL, CSA
20 - PSG480B24RM

 

has the stored power needed to keep loads running through a short duration power failure:
> 250 ms @ 24 V DC / 20 A load
> 5 sec @ 24 V DC / 1 A load

 

parallel connection possible to increase buffering time

 

flexible Buffer mode (switchable):

- Fixed mode: Buffering starts, when output voltage falls below 22 V DC
- Dynamic mode: Buffering starts, when output voltage is decreased by > 1 V.